Laserfiche WebLink
Boiler system enables based on OA temperture <br />rather than allowing hot water to be available for <br />dehumidification <br />Lead Boiler Equals 2.90 <br />Boiler Lead Rotate HAS 06 <br />Boiler 1 Start Stop Output Off Boiler 1 Sequence Nunber 3.60 <br />Boiler Start Stop Output Off Boiler Sequence llunber 1.60 <br />Boiler Start Stop Output Off Boiler Sequence llunber 2.00 <br />Lead Hot Water Pump Equals 2.60 <br />Hut Water Pump Rotation BAS 06 to <br />Pump P 4 Start! Slop Stop Pump PAA Start! Stop Start <br />Pump PA Status OR Pump PAA Status On <br />Punp-4 Faure Normal Pump -4A Fadu- INormal <br />-Eo 'ary Hot Water Pump q04 n <br />Library In Fluor Punp Start Stop Command On <br />Library In Floor Punp Status Off <br />Library In Floor Supply Temp —'F <br />Library In Floor Heat Setpoint 700 'IF <br />Library In Floor Heating Valve command 0.6 % <br />� Hot Water Reset <br />Hot Water High Supply Setpt Hot Water Lor Supply Selpt <br />150.0'F <br />Hot Water Lor OAT Se4t Hot Water High OAT SOO <br />1 0.0 60.0 'F <br />Hot Water Supply Setpl <br />154,7 'F <br />Hot Water Supply Tp 149.7'F <br />Hot water temperture set point adjusts based <br />on OA conditions rather than monitoring <br />equipment demand <br />n <br />Secordary Hot Water Pump g04A <br />Hot Water Rehm Temp 1dd.7'F <br />Boier#01 <br />Boilerg02 <br />Boilerg03 <br />Library In Fluor Punp Start Stop Command On <br />Library In Floor Punp Status Off <br />Library In Floor Supply Temp —'F <br />Library In Floor Heat Setpoint 700 'IF <br />Library In Floor Heating Valve command 0.6 % <br />� Hot Water Reset <br />Hot Water High Supply Setpt Hot Water Lor Supply Selpt <br />150.0'F <br />Hot Water Lor OAT Se4t Hot Water High OAT SOO <br />1 0.0 60.0 'F <br />Hot Water Supply Setpl <br />154,7 'F <br />Hot Water Supply Tp 149.7'F <br />Hot water temperture set point adjusts based <br />on OA conditions rather than monitoring <br />equipment demand <br />