Laserfiche WebLink
At a Glance <br />The following equipment and systems were included in your review: <br />• RTU -1 through RTU -7 <br />• VAVs served by RTU -6 <br />and RTU -7 <br />• Tracer SC System <br />Controller <br />• Hot Water System <br />At a Glance <br />• Exhaust Fans 1-6 <br />• SF -1 and SF -2 <br />Observations Recommended Action Impact <br />• The site is equipped with • Install indoor Humidity • Humidity readings are <br />minimal indoor humidity sensing sensors throughout the facility. instrumental in measuring air <br />devices. quality and comfort. <br />DILUTE <br />• Setup the existing building <br />• This mode intelligently decides <br />• Air system is not utilizing Night automation system to utilize when overnight conditions are <br />Purge ventilation strategies, but Night Purge sequences for use <br />ideal to flush stale air from building <br />the system is scheduled for 24 when system is not operating in areas. <br />hour a day operation. an Occupied condition <br />• VAVs are served by RTUs 6-7 • Change priority of supply air • Conditional static optimization <br />are resetting duct static setpoint control to ventilation allows for increased air ventilation <br />optimized for energy savings prioritization versus max VAV by avoiding reduction of fan output. <br />monitoring <br />